Can I Run Plumbing & Electrical Through Same Hole?

Home ยป Can I Run Plumbing & Electrical Through Same Hole?

ยท

If youโ€™ve ever tackled a DIY home renovation or watched a contractor drill through studs, youโ€™ve probably asked: โ€œCan I run plumbing and electrical through the same hole?โ€ Itโ€™s a practical questionโ€”after all, minimizing holes saves time and preserves structural integrity. But mixing pipes and wires isnโ€™t just about convenience. Safety, code compliance, and long-term reliability all hang in the balance. Letโ€™s break down exactly whatโ€™s allowed, whatโ€™s risky, and how to do it rightโ€”if you can.


Is It Safe to Run Plumbing and Electrical in the Same Stud Bay?

Yesโ€”but not in the exact same hole, and only under specific conditions.

According to the National Electrical Code (NEC) and most local building codes, electrical cables and water pipes can share the same wall cavity (stud bay), but they must not occupy the same drilled hole unless carefully protected.

โ€œThe NEC doesnโ€™t explicitly ban sharing stud bays, but it does require separation or protection where physical damage is possible,โ€ says Mike Holt, a leading NEC expert and electrical educator.

This distinction is crucial: same wall = often OK, same hole = usually not OK.


What Do Building Codes Actually Say?

Letโ€™s cut through the confusion with official guidance:

  • NEC Article 300.4(D) states that where electrical cables pass through holes in wood studs alongside metallic water pipes, the cable must be protected if itโ€™s within 1ยผ inches of the edge of the studโ€”but it doesnโ€™t directly prohibit sharing holes.
  • However, International Residential Code (IRC) P2603.10 requires that plumbing pipes be protected from contact with electrical grounding conductors or sharp objectsโ€”which includes NM (Romex) cable staples or nail plates.
  • Most importantly: local building inspectors often reject shared holes because of cross-contamination risk, corrosion, and future maintenance hazards.

โš ๏ธ Real-World Example: In 2023, a home inspection in Colorado flagged a remodel where PEX tubing and 12/2 Romex shared a 1-inch hole. The inspector cited โ€œpotential for cable abrasion from pipe movementโ€ and required rerouting.

Can I Run Plumbing And Electrical Through The Same Hole

Why Sharing a Hole Is Risky (Even If โ€œNot Illegalโ€)

Hereโ€™s what could go wrong if plumbing and electrical share the same drilled opening:

RiskExplanation
Pipe Leaks = Electrical ShortsEven a pinhole leak from a plumbing joint can drip onto live wires, causing shorts, arcing, or fire.
Wire Damage from Pipe MovementPlastic (PEX) or copper pipes expand/contract with temperature. Over time, this can abrade insulation on electrical cables.
CorrosionMoisture from condensation (common on cold water lines) corrodes copper conductors and junction boxes.
Code Violation During InspectionMany AHJs (Authorities Having Jurisdiction) interpret shared holes as a violation of โ€œseparation for safetyโ€ principlesโ€”even if not explicitly banned.

๐Ÿ“Š Statistic: A 2022 NAHB (National Association of Home Builders) survey found that 68% of municipal inspectors automatically fail shared plumbing-electrical holes during final walkthroughs.


When Might It Be Acceptable? (Rare Exceptions)

In very limited scenarios, sharing a hole with protection is tolerated:

  1. Non-metallic pipes only (e.g., PEX, PVCโ€”not copper or galvanized steel).
  2. Low-voltage wiring only (e.g., thermostat wires, doorbell cablesโ€”not 120V/240V circuits).
  3. Physical separation within the hole: Using a plastic divider or non-conductive sleeve to isolate systems.
  4. No joints or fittings near the hole: Ensures no future leaks occur right at the penetration.

๐Ÿ”ง Pro Tip: If you must share a bay, offset the holes vertically by at least 1โ€“2 inches. Drill the electrical hole higher (hot air rises, moisture sinks).


Best Practices: How to Run Plumbing & Electrical Safely in the Same Wall

Follow this step-by-step guide to stay compliant and safe:

  1. Plan the route together
    During framing, coordinate with your plumber and electrician. Decide who drills first. Typically, plumbing goes firstโ€”itโ€™s harder to reroute pipes than wires.
  2. Drill separate holes
    • Use a 1-inch hole for ยฝ” PEX or ยพ” copper.
    • Use a ยพ-inch hole for 14/2 or 12/2 NM cable.
    • Keep holes at least 1ยฝ inches apart horizontally or vertically.
  3. Maintain distance from edges
    Both holes should be at least 1ยผ inches from the edge of the stud. If not, install a 1/16-inch steel nail plate on the stud face (per NEC 300.4).
  4. Label and document
    Snap photos before closing walls. Note exact locations for future repairs.
  5. Use protective sleeves (if unavoidable)
    If space is extremely tight (e.g., in a retrofit), run each through separate PVC or ENT conduits inside the same oversized holeโ€”but this is a last resort.

๐ŸŒ For deeper insight into conduit types and protection rules, see the Wikipedia page on electrical conduit.


Plumbing vs. Electrical: Key Differences in Wall Installation

FactorPlumbingElectrical
Hole Size1″โ€“1ยผ” for ยฝ” pipeยพ” for standard NM cable
Max Holes per Stud60% of width (IRC R602.6)Same rule applies
Edge Distanceโ‰ฅ1ยผ” or use metal plateโ‰ฅ1ยผ” or use metal plate
FlexibilityPipes canโ€™t bend sharplyCables need gentle curves
Moisture RiskHigh (condensation/leaks)Must stay dry

๐Ÿ’ก Remember: Water and electricity donโ€™t mixโ€”ever. Even โ€œdryโ€ plumbing lines can sweat in humid climates.


FAQ Section

Q1: Can PEX tubing and Romex share a hole?

A: Technically, the NEC doesnโ€™t forbid itโ€”but most inspectors and electricians strongly advise against it. The risk of pipe movement damaging wire insulation over time is too high. Always drill separate holes.

Q2: What if the hole is already drilled and sharedโ€”do I need to fix it?

A: If youโ€™re remodeling or selling your home, yes. During inspection, this is likely to be flagged. If itโ€™s an existing, undisturbed installation with no leaks or damage, it might be grandfatheredโ€”but donโ€™t count on it.

Q3: Can I run gas lines and electrical in the same hole?

A: Absolutely not. Gas lines (even CSST) and electrical wiring must never share a penetration. This is a strict fire and explosion hazard under both NEC and IRC.

Q4: How much space should be between plumbing and electrical in a wall?

A: Thereโ€™s no universal inch rule, but 1โ€“2 inches of vertical or horizontal separation is widely accepted as safe and inspection-friendly.

Q5: Is it OK in commercial buildings?

A: Commercial codes (NEC + local amendments) are stricter. Shared penetrations usually require fire-rated sealants, separate sleeves, and engineering approval. DIY is not advised.

Q6: Whatโ€™s the penalty for violating this rule?

A: Failed inspection, mandatory rework, or even voided insurance if a fire/leak traces back to improper installation. Safety isnโ€™t worth the shortcut.


Conclusion

Soโ€”can I run plumbing and electrical through the same hole?
The short answer: Donโ€™t. While the code doesnโ€™t always explicitly ban it, the practical risks, inspector pushback, and potential hazards make it a bad idea.

Instead, drill separate holes, maintain safe spacing, and protect both systems with nail plates where needed. Your future self (and your home inspector) will thank you.

๐Ÿ”ง Found this guide helpful? Share it with a DIYer or contractor on Facebook, Pinterest, or Reddit! A little knowledge can prevent a major home disaster.

Stay safe, build smart, and always respect the code.

Comments

Leave a Reply

Your email address will not be published. Required fields are marked *